Separate running load from startup load
Running watts are the power an appliance uses after startup. Starting watts are its total brief startup demand, not an amount to add again. The calculator sums running values and either sums all starting values or adds the largest single startup increase to the total running load when starts are staggered.
Convert design watts into a generator kVA rating
Apparent power in kVA equals the selected design watts divided by power factor and 1,000. The minimum generator rating then divides that apparent power by the target operating-capacity fraction. At 0.8 power factor and 70% capacity, a 3,890 W design load requires about 6.95 kVA.
Verify the final selection against equipment data
Nameplate starting watts, voltage, phase, frequency, waveform quality, altitude, temperature, fuel type, derating, transfer equipment, duty cycle, and manufacturer surge-duration limits can change the suitable generator. Critical, medical, or code-regulated systems require review by the generator supplier or a qualified electrician.